5,000 Watt DC to AC Inverter by Wagan Tech
®
13
www.wagan.com
7. At the inverter end carefully unwrap one positive cable end and connect it to
one Positive Terminal. A spark is likely to result. This is normal.
8. Tighten the retaining nut. BE CAREFUL; DO NOT SHORT THE POSITIVE
TERMINAL TO THE GROUNDED INVERTER ENCLOSURE.
9. Continue installing the remaining positive cables.
10. Turn on the inverter. Advance the Digital Display to the Voltage display
(right green LED lit) by pressing the FUNCTION button. The display on the
front panel should show the following amounts:
#2012 (12V DC) 10.5V-13.2V DC Input
#2012-4 (24V DC) 21.0V-26.4V DC Input
#2012-8 (48V DC) 42.0V-52.8V DC Input
When the voltage reading does not fall within this range, check the
connections of the wires to the terminals on the power source and the
inverter to make sure they are secure. Also check the voltage of the power
source. Make certain that the High Temp or Overload LED Indicators are not
lit.
11. Turn OFF the inverter. The Overload and Over Temp LEDs may briefly
“flash. This is normal. The audible alarm may also emit a short “chirp. This
is also normal.
12. When you have confirmed that the appliance to be operated is turned off,
plug the appliance into one of the AC Outlets on the front panel of the
inverter.
13. Turn the inverter on.
Note: If an extension cord is used from the inverter to an appliance, limit the
extension cord length to 50 feet or less. Make sure that the cord is properly rated
to carry the appliance load. Extension cords are not to be used as permanent
wiring. Instead, use High Output Terminals and NEC compliant wiring, outlets and
installation techniques.
Charging The Battery Bank
It is not the purpose of this inverter user’s guide to provide detailed information
regarding battery charging systems. However, the user should try to augment any
charging system with either wind power or solar power. These can continue to
operate during power outages and they also reduce recharge time. If automatic
AC powered battery chargers do not provide enough charging current for a larger
battery bank, is permissible to have two automatic battery chargers connected to
the battery bank.
REGULAR LOSS OF COMMERCIAL POWER
If an inverter system is used during commercial power outages that occur daily,
configure the charging system to replace energy during the time that commercial
power is available. Replacement of battery energy always requires more than was
taken from the battery (typically 130 percent). In the example used earlier in this